·Simultaneously compensate 2~51 harmonics or compensate specified harmonics
·Fast response time <300us
·Three compensation methods of harmonic, reactive power and unbalanced load
Simultaneously filter out 2-51 harmonics or compensate user-specified harmonics
·Response time <300μs, full response time <10ms
·Choose a specific order of harmonic compensation
·Three compensation modes for reactive power and unbalanced load
·2DSP+CPLD control mode, powerful calculation function
·>97% work efficiency, low loss
·Three-level inverter circuit fast FFT and instantaneous reactive power two algorithm modes
·Modular design, stable system, can withstand -40%~+20% voltage fluctuation
·4.2-inch full-featured LCD monitoring system with PC-side enhanced software
Product number | HAPM 50A | HAPM 75/100A | HAPM 150A |
Rated compensation current (A) | 50 | 75/100 | 150 |
Dimensions (mm, width × height × depth) | 315×200×500 315×500×200 | 440×232×575 440×575×232 | 510×250×585 510×585×250 |
Net weight (kg) | 20 | 36 | 50 |
Installation method | Rack/Wall | Wall/Rack | Wall/Rack |
Line way | Back-in/up-in | Back-in/up-in | Back-in/up-in |
Air cooling mode | Intelligent air cooling 151L/Sec | ||
Noise pointer | <56dB | ||
Protection level | IP20 |
Item | project instruction | |
Electrical Specifications | Input line voltage | 380V±15% |
Phase | Three-phase three-wire, three-phase four-wire | |
frequency | 50/60Hz | |
Compensation current (phase) | 50 ~ 150A (according to the model) | |
Compensation of harmonic order | 2 ~ 50 times (can be set) | |
Power factor correction | -1 ~ +1 | |
Current limit | Rated output current | |
Parallel operation | Up to 8 modules can be connected in parallel | |
Module power consumption | <2kW | |
effectiveness | Up to 97.5% | |
CT ratio range | 150:5~6000:5 | |
Communication Interface | Dry contact | 1 EPO |
Communication | RS485 | |
Environmental requirements | Use place | Indoors, free from direct sunlight, dust, corrosive, flammable gas, oil mist, water vapor, dripping water or salt, etc. |
Working altitude | Lower than 1000 meters, use derating when higher than 1000 meters | |
Operating temperature | -10ºC ~ +40ºC | |
humidity | Less than 95%RH, no condensation |
※Selection instructions
Suitable for three-phase three-wire system and three-phase four-wire system
The compensation current can be determined through actual measurement data, or the compensation current can be calculated through detailed information of the power system (transformer, load conditions, etc.)
Three-phase four-wire system requires 3 CTs (for A-phase, B-phase and C-phase)
Three-phase three-wire system requires 2 CTs (for A phase and C phase)