CN

DRC series intelligent reactive power compensation controller

DRC series intelligent reactive power compensation controller is a new generation of control device developed with the most advanced technology.
1. Using 32-bit ARM chip, real-time data collection, power statistics, historical data storage, fault alarm, power grid harmonic analysis and other functions are realized.
2. Adhering to the human-oriented design concept, the man-machine interface is friendly, and the operation is convenient.
3. Modular assembly, streamlined appearance design. The display interface adopts LCD Chinese display, both pictures and texts, and the interface is rich in content.
4. Three-phase voltage and three-phase current sampling, real-time display of A, B, C three-phase voltage, current, power factor, active power, reactive power, total power factor, voltage total harmonic distortion rate, current total harmonic Distortion rate, frequency and other information.
5. It can realize fast dynamic reactive power compensation control, and the capacity of each channel can be set separately to ensure reliable input and no shock when the load is low.
6. In order to ensure the safety of parameter setting, this machine has a lock function. The parameter setting can only be carried out after the correct password is entered and the programming lock is unlocked.
7. It has multiple protection functions such as undervoltage, overvoltage, harmonic overrun, and current blocking.
8. Powerful data collection and processing functions can be used for data transmission, statistics and storage.
DRC series intelligent reactive power compensation controller

019.jpg

Settable parameters:

l Working power supply: 220V/AC

l Harmonic measurement: 2~31 times

l  Frequency: 50Hz                                          

l  Input delay setting: 0.02S~90S

l AC voltage sampling: 220V                                 

l Removal delay setting: 0.02S~90S

l  AC current sampling: 5A                                   

l  Input threshold setting: 0.8~1.6

l Power consumption of the whole machine: ≤15VA                                   

l  Removal threshold setting: 0.2~1.2

l  CT transformation ratio setting: 50/5~5000/5                           

l  Overvoltage protection setting: 105%~140%

l PT ratio setting: 380/100, 690/100                      

l  Undervoltage protection setting: 65%~95%

l  Target power factor setting: 0.85L~0.90C                     

l  Compensation capacity setting: 0.5kvar~300kvar

l  Control mode: automatic, input, cut

Alarm and protection functions:

l  Undercurrent alarm and removal of step capacitor

l  Overcurrent alarm

l  Overvoltage alarm and removal of step capacitor

l  Loss of pressure alarm

l  whole investment is still lower than the alarm set value COSФ

l  Wrong COSФ value alarm

l  Harmonic erratic rate of change exceeds the set value, alarm and cut off the step capacitor

l  Phase protection

1. Working voltage: 90~440V
2. Frequency range: 50Hz /60Hz ±5%
3. Input current: 0 -5A
4. Output voltage: DC 12V or AC 90V~440V
5. Maximum output channels: 16 channels 
6. Power consumption: ≤15VA
7. Working temperature: -25°C ~ + 70°C
8. Relative humidity: 40°C max. 95% non-condensing 
9. Storage function: all parameters and modes are stored in non-volatile memory
10. Display : Three-phase voltage, current, power factor, active power, reactive power, total power factor, voltage total harmonic distortion rate, current total harmonic distortion rate, frequency and other information 
11. Altitude: ≤ 2000m


Model number

Name

Cutting method

DRC-8

Control 8-way switching

Contactor

DRC-12

Control 12-way switching

Contactor, thyristor

DRC-16

Control 16-way switching

Thyristor