Hz low voltage series reactor

In the 230~900v power system,
●Suppress high-order harmonics and limit the closing inrush current to protect capacitors and switches from damage
●Avoid the amplification of harmonics and resonance of the power grid due to the access of capacitor devices
Hz low voltage series reactor

008.jpg

008.jpg

Rated frequency

50 Hz (60 hz requires special instructions)

Rated insulation level

3 kv/min

Temperature rise limit of each part

Iron core ≤85 K coil ≤90K

Reactor noise

45dB

Overload capacity

≤1.35 Qn

Insulation material temperature resistance

 F H level (180℃)

Altitude

≤ 2000 m

Environmental standards

No corrosive gas, conductive, explosive dust

Temperature range

-25~50 ℃

Seismic strength

Level 8

cooling method

Air-cooled


model

System voltage (V)

Capacity (kvar)

Matching capacitor voltage (V)

Terminal voltage (V)

Rated current (A)

Reactance value (Ω)

Inductance value (mH)

Matched capacitor parameters (kvar)

Standard compensation three-phase reactor 480V

Hz480-L-1.05/7

400V

1.05

480

19.40

18.04

1.08

3.42

15

Hz480-L-2.1/7

400V

2.10

480

19.40

36.08

0.54

1.71

30

Hz480-L-2.8/7

400V

2.80

480

19.40

48.11

0.40

1.28

40

Hz480-L-3.5/7

400V

3.50

480

19.40

60.14

0.32

1.03

50

Standard compensation three-phase reactor 525V

Hz525-L-2.8/14

400V

2.80

525

42.44

21.99

1.93

6.14

20

Hz525-L-4.2/14

400V

4.20

525

42.44

32.99

1.29

4.09

30

Hz525-L-7.0/14

400V

7.00

525

42.44

54.99

0.77

2.46

50

Standard compensation single-phase reactor 280V

Hz280-L-0.35/7

400V

0.35

280

19.60

17.86

1.10

3.49

5

Hz280-L-0.7/7

400V

0.70

280

19.60

35.71

0.55

1.75

10

Hz280-L-1.4/7

400V

1.40

280

19.60

71.43

0.27

0.87

20